Backflow Construction Guide

All industrial and commercial customers are required by ordinance to install and maintain backflow prevention assemblies at every water service connection to Charlotte Water. This includes domestic, irrigation, fire line services, and swimming pool meters.

Before beginning any construction project, industrial and commercial customers must submit construction plans to Mecklenburg County Land Use and Environmental Services. There, Charlotte Water will evaluate your plans and inform you of the requirements for a backflow device.

When the backflow prevention assembly is installed, call Charlotte Water Backflow at 704-336-2456 to request an inspection. A Charlotte Water approved and certified tester must test the device upon installation and annually thereafter.

Approval Procedures for CLTWater

Required Backflow Preventer Installations

PRIOR TO INSTALLING A CLTWater‐REQUIRED BACKFLOW PREVENTER, THE DESIGNER AND/OR INSTALLER MUST OBTAIN CLTWater APPROVAL OF THE INSTALLATION PLAN

(Designer And Installer Must Be Currently Licensed By The Appropriate State Of North Carolina Licensing Board):

  1. Complete a CLTWater “Backflow Service Application” (BSA).  Be sure to provide all information listed in the form.  Failure to do so may delay approval.
  2. Submit the BSA, along with any required plan information*, to the Commercial Counter at Building Standards (2145 Suttle Ave., Charlotte, NC  28208‐5237).    

    *Note: Some projects may not require drawings for review, but may instead be managed via on‐site assistance from a CLTWater Backflow Prevention Construction Inspector.  The designer and/or contractor is responsible for contacting CLTWater to determine whether or not submittal of plan drawings is required.  All locations for CLTWater backflow preventers require CLTWater approval prior to installation.

  3. Plan review is handled via the Building Standards’ commercial plan review process.  All drawing submittals must conform to CLTWater’s Backflow Prevention Plan Submittal Requirements list, unless instructed otherwise.  Revise and resubmit plan drawings per plan review comments as needed.
  4. Wait for CLTWater approval of your BSA and plan before beginning the installation.  Approved plan drawings will be stamped by CLTWater as such.  Projects managed via site assistance will receive an approval notice from the Backflow Prevention Construction Inspector.  The designer and/or installer shall be responsible for obtaining approvals required by all other agencies.

INSTALLER MUST OBTAIN FIELD APPROVAL OF THE INSTALLATION FROM A CLTWater BACKFLOW PREVENTION CONSTRUCTION INSPECTOR PRIOR TO PLACING THE WATER SYSTEM IN SERVICE

(Certain Exceptions Will Be Allowed for Retrofit Projects at Existing Facilities):

  1. Call the Backflow Construction Inspector to resolve any problems encountered in the field.  Installing backflow preventers in a location and/or manner other than that specified on the plans approved by CLTWater requires approval from the Inspector.  Obtain site assistance by calling 704‐391‐5188.
  2. Obtain approval of the installation(s) by calling 704‐391‐5188 to request inspection.  Inspection service will be provided within three working days from the date of request. Approval by the Backflow Inspector is required prior to issuance of the Certificate of Occupancy (CO).
  3. Verify installation approval by contacting the Inspector or by calling 704‐391‐5188.  Correct all deficiencies per Inspector’s instructions and obtain reinspection and inspection results as above. CLTWater is not responsible for delay of CO issuance when procedures above are not followed.  
  4. Prior to placing the water system(s) in service, have the backflow preventer(s) tested ASAP and submit a copy of the test report(s) to CLTWater within 10 days of the Inspector’s approval of the installation.

Guide for Determining What Type Backflow Preventer Charlotte Water (CLT Water) Will Require

Irrigation Systems

As of March 24, 2003, all irrigation systems now require a Reduced Pressure Principle Assembly (RP). Irrigation systems with a Double Check Valve Assembly (DCVA) that has been previously approved and inspected by CLT Water are “grandfathered” until such time that the DCVA needs replacement.

Fire Protection Systems

Characteristics That Require Installing a Reduced Pressure Principle Assembly (RP):

(1) presence of a Fire Department Connection (FDC)

(2) chemicals (glycol or other types) added to the water in any part of the system,

(3) system involving a water storage facility (ex.: above- or below-ground tanks, surface reservoirs),

(4) back-up provision for using an auxiliary water source (ex.: private well, pond, river).

Note: State and local Codes do not allow a private system to be served by an auxiliary water source while connected to CLT Water’s public water system. An air gap separation must be maintained.

Characteristics That Require Installing a Double Check Valve Assembly (DCVA) (Minimum Protection):

(1) system not involving any characteristics for which CLT Water requires an RP,

(2) system carrying only air (“dry system”),

Domestic, Process, and Combination Systems

Characteristics That Require Installing a Reduced Pressure Principle Assembly (RP):

(1) system involving any of the characteristics listed above for which CLT Water requires an RP,

(2) system with any type booster pump or pressure washer equipment

(3) system involving any piping at an elevation which is greater than fifty (50) feet above the meter piping,

(4) system which involves water that has been or is being recirculated (ex.: boiler, chiller, machinery cooling)

(5) system used for chemical mixing or chemical feed activities (ex.: golf course operations, industrial processes),

(6) system involving tanks, lines, steam boilers, or vessels that carry sewage, toxic, or radioactive substances.

(7) system which involves injection or aspiration of chemicals into any portion of the system (ex.: sanitizer system at multi-compartment sink, fertigation system)

(8) system with sewage pump or water-operated sewage sump ejector

(9) system with any non-potable branch or connected to any equipment serving a non-potable function (ex.: irrigation branch, decorative water features (fountain, waterfall, etc.), parts washer).

(10) back-up provision for using an auxiliary water source (ex.: private well, pond, river),

Note: State and local Codes do not allow a private system to be served by an auxiliary water source while connected to CLT Water’s public water system. An air gap separation must be maintained.

Characteristics That Require Installing a Double Check Valve Assembly (DCVA) (Minimum Protection):

(1) system not involving any characteristics for which CLT Water requires an RP

Types of Facilities That Require Installing a Reduced Pressure Principle Assembly (RP)

Facilities listed here may not necessarily involve any of the aforementioned water system characteristics, but are required to install an RP on their domestic, process, and combination systems due to the type of activities and/or materials used in the facilities and their potential to create a health hazard.

(1) Battery manufacturer

(2) Brewery, dairy, or bottling plant

(3) Buildings with any tenant occupancy

(4) Cannery

(5) Carwash

(6) Chemical processing plant

(7) Dental service of any type

(8) Dry cleaners

(9) Dye works

(10) Exterminating company

(11) Film lab

(12) Grocery store with injection or aspiration of chemicals into a portion of the system (ex.: sanitizer system in meat department)

(13) Hospital, medical office, or health service facility of any type

(14) Laboratory

(15) Laundry (commercial) – except if only self-service

(16) Lawn-care service, fertilizer plant

(17) Metal plating or processing facility

(18) Morgue, mortuary

(19) Nursing home, including “assisted living” facilities

(20) Pharmaceutical plant

(21) Power plant

(22) Sewage collection or treatment facility

(23) Swimming pool – except those excluded by Sec. 23-113

(24) Tire manufacturer

(25) Veterinary service of any type (ex.: hospital, clinic, or office)

(26) Water-front facilities (ex.: boat dock, marina)

(27) Any facility or system, which is insufficiently accessible for inspection by a CLT Water backflow inspector

Types of Facilities That Require Installing a Double Check Valve Assembly (DCVA)

(Minimum Protection):

Facilities listed here cannot involve any of the aforementioned water system characteristics nor facility types for which CLT Water requires an RP.

(1) Distillery

(2) Gas station

(3) Mobile home park

(4) Restaurant without injection or aspiration of chemicals into a portion of the system (ex.: sanitizer system at multi-compartment sink)

(5) Self-service laundry

(6) Other facilities for which no other assembly is otherwise specified

Note: each private water system will be evaluated on a case-by-case basis. In some cases, the requirement may differ from this list.

Backflow Construction Design Specifications

Double Check Valve Assemblies